Short Cycling

Pump short cycles (turns On and Off rapidly).
Pump short cycles (turns On and Off rapidly).
WARNING: Please use caution while handling your pump control panel. We have designed them with the highest safety standards in mind, however they are complex electronics and can cause death or serious injury if used improperly. Only follow the instructions provided in these videos and contact our support team if you are unsure of what to do.
WARNING: Please use caution while handling your pump control panel. We have designed them with the highest safety standards in mind, however they are complex electronics and can cause death or serious injury if used improperly. Only follow the instructions provided in these videos and contact our support team if you are unsure of what to do.
Verify Pumps Off and Lead Pump On floats are in the correct order in the tank.
Verify Pumps Off and Lead Pump On floats are in the correct order in the tank.
Verify Pumps Off float and Lead Pump On float are wired correctly inside the control panel.
Verify Pumps Off float and Lead Pump On float are wired correctly inside the control panel.
Is panel still short cycling?
Yes
No
Turn off power. Tag and remove floats.
Turn off power. Tag and remove floats.
Reconnect power to panel. Place one piece of insulated jumper wire across Pump Off float terminals. Place another insulated jumper wire across Pump On float terminals. One pump should turn on and remain on for the duration the jumper wires are applied to the panel.
Reconnect power to panel. Place one piece of insulated jumper wire across Pump Off float terminals. Place another insulated jumper wire across Pump On float terminals. One pump should turn on and remain on for the duration the jumper wires are applied to the panel.
Remove both jumper wires. Pump should turn off. Place one piece of insulated jumper wire across Pump Off float terminals. Place another insulated jumper wire across Pump On float terminals.
Remove both jumper wires. Pump should turn off. Place one piece of insulated jumper wire across Pump Off float terminals. Place another insulated jumper wire across Pump On float terminals.
Did the panel operate properly with jumper wires, but not float switches?
Yes
No
{"name":"Short Cycling", "url":"https://www.quiz-maker.com/QRWMBJN","txt":"Pump short cycles (turns On and Off rapidly)., WARNING: Please use caution while handling your pump control panel. We have designed them with the highest safety standards in mind, however they are complex electronics and can cause death or serious injury if used improperly. Only follow the instructions provided in these videos and contact our support team if you are unsure of what to do., Verify Pumps Off and Lead Pump On floats are in the correct order in the tank.","img":"https://cdn.poll-maker.com/48-1624822/pump-short-cycles.jpg?sz=1200-00000021161000005300"}