Test Alarm Function

Follow along to test your alarm's function.
Follow along to test your alarm's function.
WARNING: Please use caution while handling your pump control panel. We have designed them with the highest safety standards in mind, however they are complex electronics and can cause death or serious injury if used improperly. Only follow the instructions provided in these videos and contact our support team if you are unsure of what to do.
WARNING: Please use caution while handling your pump control panel. We have designed them with the highest safety standards in mind, however they are complex electronics and can cause death or serious injury if used improperly. Only follow the instructions provided in these videos and contact our support team if you are unsure of what to do.
Turn the Control On/Off switch to the Off position if applicable or disconnect all power to the panel. Images may vary depending on the panel and features.
Turn the Control On/Off switch to the Off position if applicable or disconnect all power to the panel. Images may vary depending on the panel and features.
Place a jumper wire between positions 9 and 10.
Place a jumper wire between positions 9 and 10.
Reconnect power to the panel. Turn the Control On/Off switch to the On position. All of the following should happen:
  1. The alarm should activate
  2. Lag/Alarm float LED should illuminate and Alarm LED should illuminate
  3. Test the horn silence relay by pressing the Test/Normal/Silence switch. The horn should be deactivated.
Reconnect power to the panel. Turn the Control On/Off switch to the On position. All of the following should happen:
  1. The alarm should activate
  2. Lag/Alarm float LED should illuminate and Alarm LED should illuminate
  3. Test the horn silence relay by pressing the Test/Normal/Silence switch. The horn should be deactivated.
Did the circuit board operate as indicated in the previous step?
Yes
No (Go to Alarm Circuit Troubleshooting)
{"name":"SJE Rhombus Test Alarm Function", "url":"https://www.quiz-maker.com/QH7XV37","txt":"Follow along to test your alarm's function., WARNING: Please use caution while handling your pump control panel. We have designed them with the highest safety standards in mind, however they are complex electronics and can cause death or serious injury if used improperly. Only follow the instructions provided in these videos and contact our support team if you are unsure of what to do., Turn the Control On\/Off switch to the Off position if applicable or disconnect all power to the panel. Images may vary depending on the panel and features.","img":"https://cdn.poll-maker.com/49-1657816/sje-duplex-models-2.jpg?sz=1200-00000004721000005300"}
Powered by: Quiz Maker